Outlets Available |  | 2 - 20 amp (unswitched)
|
 |
Load Ratings |  | 20A at 120 volts, single phase, 50-60 Hz; full load regulation 1%.
|
 |
Endurance Test |  | 1,000 surges of 6,000 volts, 3,000 amperes, SRV <400 volts, no failures, L-N (ground wire protection) mode, U.S. Gov't. Mode 1.
|
 |
Limiters |  | Series surge reactor current limiter; cascaded, auto-tracking dual polarity voltage limiters; dual pulse inverters. Parameters optimized for switch-mode power supply protection.
|
 |
Clamping Voltage Onset |  | 172 volts nominal; 2 volts above peak line voltage (auto-tracking).
|
 |
EMI/RFI Filter Response |  | (bi-directional, wave tracking): With 50 ohm Rg load: 3db at 5kHz; 26dB at 100kHz; 38dB at 300kHz.
|
 |
Let-Through Slew Rate |  | 5,000 volt/microsecond disturbance reduced to 28v/microsecond within AC power wave envelope, and less than 10v/microsecond outside the power wave envelope.
|
 |
Maximum Applied Surge Pulse Joule Rating |  | Unlimited rating (due to surge current limiting) (8x20microsecond).
|
 |
Maximum Applied Surge Pulse Voltage |  | 6,000 volts (1.2 x 50 microseconds) (Industry Standard rating).
|
 |
Maximum Applied Surge Pulse Current |  | >100,000 amperes (unlimited due to current limiting) (8 x 20 microseconds).
|
 |
Endurance, C62.41-1991 (formerly IEEE 587) Category B3 (C1) pulses |  | 2kv>100,000; 4kv>10,000; 6kv>1,000 (NRTL verified).
|
 |
Dimensions |  | 3" H x 8.5" W x 4" D
|
 |
Weight |  | 6.5 lbs.
|
 |